Sinumerik Alarm 300001 Axis %1 drive number %2 not possible


Sinumerik Alarm 300001 Axis %1 drive number %2 not possible

Parameters:
%1 = NC axis number
%2 = Drive number

Definitions:
On powering up the drives, the NCK-specific machine data 13010 DRIVE_LOGIC_NR was checked for impermissible inputs. In the MD, a drive logic number is entered that can be selected as required within the established limits (drive number 0 = “No drive avail- able”). Numbers greater than 15 are not allowed, nor may the same number be used more than once. The MD array must be configured without spaces, i.e. as soon as the logical drive number 0 is selected once, it is necessary for the logical drive number 0 to be entered in all MDs with a higher location index [p].

Reactions:
– NC not ready.
– Channel not ready.
– NC Stop on alarm.
– NC Start disable in this channel.
– The NC switches to follow-up mode.
– Alarm display.
– Interface signals are set.

Remedy:
Please inform the authorized personnel/service department. Check MD DRIVE_LOGIC_NR for numbers greater than 15 or for gaps in the machine axis indices.

Program Continuation:
Switch control OFF – ON.