Sinumerik Alarms

Siemens Sinumerik Alarms Errors SINUMERIK 840D/840Di/810D

Sinumerik Alarm 300747 Axis %1 drive %2 monitoring cycle time MD 1300 invalid

Sinumerik Alarm 300747 Axis %1 drive %2 monitoring cycle time MD 1300 invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: Check and, if necessary, correct MD…

Sinumerik Alarm 300748 Axis %1 drive %2 monitoring cycle times of both axes differ

Sinumerik Alarm 300748 Axis %1 drive %2 monitoring cycle times of both axes differ Parameters: %1 = NC axis number %2 = Drive number Definitions: The monitoring cycles set in…

Sinumerik Alarm 300749 Axis %1 drive %2 conversion factor between motor and load too large

Sinumerik Alarm 300749 Axis %1 drive %2 conversion factor between motor and load too large Parameters: %1 = NC axis number %2 = Drive number Definitions: The conversion factor from…

Sinumerik Alarm 300767 Axis %1 drive %2 natural frequency > Shannon frequency

Sinumerik Alarm 300767 Axis %1 drive %2 natural frequency > Shannon frequency Parameters: %1 = NC axis number %2 = Drive number Definitions: The natural frequency of a speed setpoint…

Sinumerik Alarm 300771 Axis %1 drive %2 asynchronous mode: converter frequency invalid

Sinumerik Alarm 300771 Axis %1 drive %2 asynchronous mode: converter frequency invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: Only a converter frequency of 4 kHz…

Sinumerik Alarm 300773 Axis %1 drive %2 asynchronous mode: feedforward control structure not possible

Sinumerik Alarm 300773 Axis %1 drive %2 asynchronous mode: feedforward control structure not possible Parameters: %1 = NC axis number %2 = Drive number Definitions: In asynchronous mode (select by…

Sinumerik Alarm 300763 Axis %1 drive %2 emergency retraction mode/generator mode invalid

Sinumerik Alarm 300763 Axis %1 drive %2 emergency retraction mode/generator mode invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: Value specified by the NC via a…

Sinumerik Alarm 300764 Axis %1 drive %2 emergency retraction mode/generator mode not possible

Sinumerik Alarm 300764 Axis %1 drive %2 emergency retraction mode/generator mode not possible Parameters: %1 = NC axis number %2 = Drive number Definitions: Emergency retraction/Generator operation is only possible…

Sinumerik Alarm 300780 Axis %1 drive %2 zero load current > rated motor current

Sinumerik Alarm 300780 Axis %1 drive %2 zero load current > rated motor current Parameters: %1 = NC axis number %2 = Drive number Definitions: The no-load current of the…

Sinumerik Alarm 300781 Axis %1 drive %2 zero load current > rated current of power section

Sinumerik Alarm 300781 Axis %1 drive %2 zero load current > rated current of power section Parameters: %1 = NC axis number %2 = Drive number Definitions: On the basis…

Sinumerik Alarm 300774 Axis %1 drive %2 asynchronous mode: changeover speed invalid

Sinumerik Alarm 300774 Axis %1 drive %2 asynchronous mode: changeover speed invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: In mixed operation MSD/AM (MD 1465 >…

Sinumerik Alarm 300766 Axis %1 drive %2 blocking frequency > Shannon frequency

Sinumerik Alarm 300766 Axis %1 drive %2 blocking frequency > Shannon frequency Parameters: %1 = NC axis number %2 = Drive number Definitions: The blocking frequency of a speed setpoint…

Sinumerik Alarm 300862 Axis %1 drive %2 emergency retraction mode/generator mode already active

Sinumerik Alarm 300862 Axis %1 drive %2 emergency retraction mode/generator mode already active Parameters: %1 = NC axis number %2 = Drive number Definitions: Emergency retraction or generator mode already…

Sinumerik Alarm 300863 Axis %1 drive %2 emergency retraction mode/generator mode invalid

Sinumerik Alarm 300863 Axis %1 drive %2 emergency retraction mode/generator mode invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: Value specified by the NC via a…

Sinumerik Alarm 300768 Axis %1 drive %2 numerator bandwidth > double blocking frequency

Sinumerik Alarm 300768 Axis %1 drive %2 numerator bandwidth > double blocking frequency Parameters: %1 = NC axis number %2 = Drive number Definitions: The bandwidth numerator of a current…

Sinumerik Alarm 300769 Axis %1 drive %2 denominator bandwidth > double natural frequency

Sinumerik Alarm 300769 Axis %1 drive %2 denominator bandwidth > double natural frequency Parameters: %1 = NC axis number %2 = Drive number Definitions: The bandwidth denominator of a current…

Sinumerik Alarm 300770 Axis %1 drive %2 format error

Sinumerik Alarm 300770 Axis %1 drive %2 format error Parameters: %1 = NC axis number %2 = Drive number Definitions: The calculated filter coefficients of a bandstop filter are beyond…

Sinumerik Alarm 300772 Axis %1 drive %2 asynchronous mode: speed control gain too high

Sinumerik Alarm 300772 Axis %1 drive %2 asynchronous mode: speed control gain too high Parameters: %1 = NC axis number %2 = Drive number Definitions: The value in MD 1451:…

Sinumerik Alarm 300775 Axis %1 drive %2 fixed link voltage of axes differ

Sinumerik Alarm 300775 Axis %1 drive %2 fixed link voltage of axes differ Parameters: %1 = NC axis number %2 = Drive number Definitions: An unequal fixed voltage MD1161: $MD_FIXED_LINK_VOLTAGE…

Sinumerik Alarm 300776 Axis %1 drive %2 measuring circuit monitoring must be active

Sinumerik Alarm 300776 Axis %1 drive %2 measuring circuit monitoring must be active Parameters: %1 = NC axis number %2 = Drive number Definitions: On FDD: The control is disabled,…

Sinumerik Alarm 300777 Axis %1 drive %2 rotor position identification current too high

Sinumerik Alarm 300777 Axis %1 drive %2 rotor position identification current too high Parameters: %1 = NC axis number %2 = Drive number Definitions: The current set in MD1019: $MD_CURRENT_ROTORPOS_IDENT…

Sinumerik Alarm 300778 Axis %1 drive %2 generator mode: converter frequency rotor position identification

Sinumerik Alarm 300778 Axis %1 drive %2 generator mode: converter frequency rotor position identification Parameters: %1 = NC axis number %2 = Drive number Definitions: When selecting the rotor position…

Sinumerik Alarm 300779 Axis %1 drive %2 motor moment of inertia less than or equal to zero

Sinumerik Alarm 300779 Axis %1 drive %2 motor moment of inertia less than or equal to zero Parameters: %1 = NC axis number %2 = Drive number Definitions: The value…

Sinumerik Alarm 300765 Axis %1 drive %2 measurement of DC link voltage not possible

Sinumerik Alarm 300765 Axis %1 drive %2 measurement of DC link voltage not possible Parameters: %1 = NC axis number %2 = Drive number Definitions: If the fixed voltage MD…

Sinumerik Alarm 300786 Axis %1 drive %2 field weakening speed invalid

Sinumerik Alarm 300786 Axis %1 drive %2 field weakening speed invalid Parameters: %1 = NC axis number %2 = Drive number Definitions: The value in MD 1142: $MD_FIELD_WEAKENING_SPEED (threshold speed…

Sinumerik Alarm 300799 Axis %1 drive %2 data backup and reboot required

Sinumerik Alarm 300799 Axis %1 drive %2 data backup and reboot required Parameters: %1 = NC axis number %2 = Drive number Definitions: Since drive machine data have been changed,…

Sinumerik Alarm 300858 Axis %1 drive %2 generator mode: response voltage > switch-off threshold

Sinumerik Alarm 300858 Axis %1 drive %2 generator mode: response voltage > switch-off threshold Parameters: %1 = NC axis number %2 = Drive number Definitions: The sum of the values…

Sinumerik Alarm 300859 Axis %1 drive %2 generator mode: response voltage > monitoring threshold

Sinumerik Alarm 300859 Axis %1 drive %2 generator mode: response voltage > monitoring threshold Parameters: %1 = NC axis number %2 = Drive number Definitions: The value in MD 1631:…

Sinumerik Alarm 300860 Axis %1 drive %2 generator mode: emergency retraction speed > max. motor speed

Sinumerik Alarm 300860 Axis %1 drive %2 generator mode: emergency retraction speed > max. motor speed Parameters: %1 = NC axis number %2 = Drive number Definitions: The value entered…

Sinumerik Alarm 300861 Axis %1 drive %2 generator mode: minimum axis speed > max. motor speed

Sinumerik Alarm 300861 Axis %1 drive %2 generator mode: minimum axis speed > max. motor speed Parameters: %1 = NC axis number %2 = Drive number Definitions: The value in…

Sinumerik Alarm 300787 Axis %1 drive %2 asynchronous mode: feedforward control gain out of range

Sinumerik Alarm 300787 Axis %1 drive %2 asynchronous mode: feedforward control gain out of range Parameters: %1 = NC axis number %2 = Drive number Definitions: If motor inertia and…

Sinumerik Alarm 300788 Axis %1 drive %2 parameterization error in current control adaption

Sinumerik Alarm 300788 Axis %1 drive %2 parameterization error in current control adaption Parameters: %1 = NC axis number %2 = Drive number Definitions: The upper current limit in MD…

Sinumerik Alarm 300950 Axis %1 drive %2 is not safely referenced

Sinumerik Alarm 300950 Axis %1 drive %2 is not safely referenced Parameters: %1 = Axis number %2 = Drive number Definitions: No stop reaction is initiated. The message will be…

Sinumerik Alarm 300951 Axis %1 drive %2 test stop is running

Sinumerik Alarm 300951 Axis %1 drive %2 test stop is running Parameters: %1 = Axis number %2 = Drive number Definitions: The pulses are deleted. 1. If the positive acknowledgement…

Sinumerik Alarm 300952 Axis %1 drive %2 acceptance test mode is active

Sinumerik Alarm 300952 Axis %1 drive %2 acceptance test mode is active Parameters: %1 = Axis number %2 = Drive number Definitions: The acceptance test mode has been activated by…